Answer
Nov 27, 2019 - 04:08 AM
You would need to replace the floor sensor as the Devireg uses a 15K NTC type whereas the Touch-e uses 10k.
The neoStat-e does give the option to switch (via software) between 10,12 and 15K so might be the better option for you. https://www.heatmisershop.co.uk/heatm...
The neoStat-e does give the option to switch (via software) between 10,12 and 15K so might be the better option for you. https://www.heatmisershop.co.uk/heatm...